Design optimization
Comparison of two systems’ performance
Thermal displacement ventilation
(B)250 cfm per diffuser 64 oF supply temp
(A)150 cfm per diffuser 56 oF supply temp
Floor temperature
Temperature distribution
in a vertical cross section
BACKGROUND: There are two options when a displacement ventilation system is employed. System (A) was originally q proposed system but CFD data shows that the system (A) may cause temperature gradient problem. The newly proposed system (B) resolved the temperature gradient issue while maintaining design temperature, 74F.